The Type WSA- and WSA-S walk-in
fume hoods are carefully engineered with air foil surfaces
curved to the air flow path, thereby creating a smoother air
flow pattern that can effectively remove air at a lower face
velocity. Thus, less room air is used when compared to a standard
or conventional fume hood.
Lab Fabricators fume hood superstructures are shipped
factory assembled with the light fixture, work surface, service
fixtures and electricals installed and tested. All hoods are
available in lengths from 3-0" to 100-0" and
may be customized to meet each users specific requirements.
The WSA- and WSA-S walk-in
fume hood superstructures are furnished with:
- The hood exterior is fabricated of 18 gauge, zinc-coated
and bondarized steel with a chemical resistant enamel to match
the base cabinet (furnished upon request).
- The interior of the WSA- hood
is made of 1/4" thick, special heat, solvent and reagent
resistant composition stone that is treated with a chemical
resistant, clear vinyl for added protection. (Additional
hood liners are available upon request, including a white
modified resin/fiberglass, fiberglass reinforced polyester
(FRP), and white polypropylene.) The WSA-S hood
is furnished with 18 gauge, T304 or T316 stainless steel
interior lining, baffles and adjustable dampers in a flat
sheet construction. (A seamless welded interior shell is
also available upon request.)
- The fume hood baffles have three adjustable air flow dampers
at the top, center and bottom for adjustment to light or heavy
gases.
- The interior of the hood is illuminated with a vapor-proof
incandescent light fixture for added visibility.
- Two vertically rising front sashes are glazed with 1/4" thick,
laminated safety glass and counter balanced with lead weights
for fingertip movement. Sash stops are available, upon request,
to further restrict the face opening of the hood.
- If the hood is furnished with a blower, the blower can be
enclosed within the hood ceiling or shipped separate. The
blower housing and wheel are coated
with a highly chemical resistant epoxy coating for extra protection
against corrosion.
Typical WSA- and WSA-S Walk-In
Fume Hoods
Catalog
Number |
Overall
Size L x H |
Face
Opening* |
Exhaust
CFM @ 100 FPM face velocity |
Exh.
S.P |
Standard
Exhaust Blower Included |
Composition
Stone Lined Interior |
Stainless
Steel Lined Interior |
| WSA-4B |
WSA-4SB |
48" |
114" |
7.0 SF |
700 CFM |
1/4" |
D8C |
| WSA-5B |
WSA-5SB |
60" |
114" |
9.3 SF |
930 CFM |
1/4" |
D9C |
| WSA-6B |
WSA-6SB |
72" |
114" |
11.7 SF |
1170 CFM |
3/8" |
KE-11 |
| WSA-7B |
WSA-7SB |
84" |
114" |
14.0 SF |
1400 CFM |
1/4" |
KE-12 |
| WSA-8B |
WSA-8SB |
96" |
114" |
16.3 SF |
1630 CFM |
1/4" |
KE-12 |
| WSA-4 |
WSA-4S |
48" |
101" |
7.0 SF |
700 CFM |
1/4" |
None |
| WSA-5 |
WSA-5S |
60" |
101" |
9.3 SF |
930 CFM |
1/4" |
None |
| WSA-6 |
WSA-6S |
72" |
101" |
11.7 SF |
1170 CFM |
3/8" |
None |
| WSA-7 |
WSA77S |
84" |
101" |
14.0 SF |
1400 CFM |
1/4" |
None |
| WSA-8 |
WSA-8S |
96" |
101" |
16.3 SF |
1630 CFM |
1/4" |
None |
| *Note: |
The total CFM requirement of the standard blowers are
based on the lower window sash being closed and the upper
sash being open during fume hood operation. |
| *Note: |
Blowers, where required, may be shipped either
factory installed within the hood ceiling or separate from
the hood superstructure. |
| Note: |
A complete system, including chemical resistant duct
work, is available. |
The WSA- and WSA-S walk-in fume hoods may be customized by adding
any of the following accessories:
Working Floor
- Cast epoxy resin (flat or indented to
retain spills)
- "Solid Bond" stainless
steel
Counter High Work Top
Service Fixtures
- Remotely controlled angle hose connectors
for cold water, air, gas, vacuum, etc.
Cup Sinks
- Panel mounted polypropylene or chrome plated
Electricals
- Duplex or single receptacles (Specify voltage
and amperage required.)
- Motor starter or on/off
switch for exhaust blower
Light Fixture
- Two tube fluorescent fixture (less bulbs),
factory wired to a light switch
- Explosion-proof
incandescent fixture (less bulb), 150-300 watt
Safety Guard Low Face Velocity Alarm
- Complied with OSHA
regulations
- Factory installed and prewired
|
|